DIN Rail Mount Transmitters with RFID Communications

  • TXDIN401 Temperature Transmitter Accepts Pt100 or Ni100 RTD Inputs and Types J/K/T/E/R/S/B/N Thermocouples
  • TXDIN402 Accepts Process Voltage, Current or Resistance Input
  • User Configurable via TX400-RFID (NFC) Programmer and Configuration Software
  • High Accuracy
  • 16-Bit Conversion
  • Isolated
  • Linearized
  • Transmitters Have 2624 Word Non-Volatile Memory (Circular Buffer) for Data-Logging with User-Selectable Sampling Time
  • FREE Downloadable RF Programmer Configuration Software from OMEGA

Process Measurement and Control Instruments – View related products

Description

The TXDIN401 and TXDIN402 DIN rail mount transmitters transform a temperature or process signal into a linearized 2-wire loop-powered 4 to 20 mA output. Model TXDIN401 is a temperature transmitter that accepts Pt100 or Ni100 RTD and Types J/K/T/E/R/S/B/N thermocouples. Model TXDIN402 is a process input transmitter that accepts voltage, current or resistance input. The characteristics of these converters ensure high precision on the reading scale with 16-bit conversion. The 4 to 20 mA output can be scaled based on the desired input range.

The programming procedure uses an RFID (NFC) mode with the dedicated TX400-RFID programmer that allows the user to make all calibrations and settings quickly and without the need to power and connect up the transmitter. Simply connect the TX400-RFID programmer to the USB port of your PC, start the RF Programmer configuration software and place the transmitter on top of the TX400-RFID programmer to establish communications. These transmitters are also provided with a data logging function for the input signal. Transmitters have a non-volatile memory (circular buffer) for data-logging with user-selectable sampling time. The user selects the sampling time (1 to 3600 seconds) and then each time the 4 to 20 mA loop powers the device, the input value is stored to non-volatile memory.

Using the TX400-RFID programmer along with the RF Programmer configuration software (software is a free download from OMEGA) the user can:
Completely configure the transmitter including scaling the 4 to 20 mA output to desired input range
Implement field calibration to compensate for gain and offset errors
Download logged data to PC for visualization and printing

Specifications
RTD Input Types and Ranges (TXDIN401 Only)
    Pt100 (a = 0.00385): 2, 3, or 4-wire connection, -200 to 600°C (-328 to 1112°F)
Ni100 (a = 0.00618): 2, 3, or 4-wire connection, -60 to 180°C (-76 to 356°F)
Thermocouple Input Types (TXDIN401 Only): J/K/T/E/R/S/B/N/mV
Process Input Types and Ranges (TXDIN402 Only):
    Voltage: 0 to 10 V
Current: 0 to 20 mA (4 to 20 mA default)
Resistance: 0 to 4000 Ω
Output Resolution: 2 µA
Over-Range Output: fs + 5°C
Under-Range Output: fs – 5°C
Output Error (Failure): Selectable between 21 mA or 3.8 mA
Current Output Protection: 30 mA approx
Rejection: 50 to 60 Hz
Maximum Transmission Error: 0.1% FS or 0.2°C whichever is greater
Sampling Time: 300 msec
Response Time (10 to 90%): 600 msec
Non-Volatile Memory (Circular Buffer) for Data Logging: 2624 word
Cable Resistance: 20 Ω max
Temperature Coefficient: < 100 ppm
Power: 2-wire loop powered; operating range 6 to 32 Vdc
Isolation: Galvanic, 1 KVac input/output
Operating Environment: -40 to 85°C (-40 to 185°F), 30 to 90% RH (non condensing)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Mounting: 3 mm DIN rail
Material: Enclosure, polycarbonate; front panel, silicone
Enclosure Rating: NEMA 1 (IP20) according to CE, EN 61000-6-4, EN 61000-6-2
Programming: Wireless with RFID technology (NFC)
Software: Windows® XP/7/8 (32-bit and 64-bit), Windows 10 (64-bit)
Connection: Screw terminals
Weight: 30 g (1.05 oz) approx
Dimensions: 90 H x 18 W x 64 mm D (3.54 x 0.71 x 2.52″)

Free Phone 0800 488 488

International +44(0) 161 777 6611

24 hr. FAX 0161 777 6622

Website: http://www.omega.co.uk/

 

You may also like...